Building Technologies 74 319 0617 0 a 17.04.2008 25/180
en
7. Note with underfloor and ceiling heating systems:
The limit thermostat must be set to the correct value.
During the functional test, the flow temperature may not exceed the maximum permissible
level (usually 55 °C). If it does, proceed immediately as follows:
Either close the valve manually, or
Switch off the pump, or
Close the pump isolating valve
8. Switch on power supply. The display must show something (e.g. time of day). If not, the
reason may be one of the following:
No mains voltage present
Main fuse defect
Main switch not set to ON
General information about operation
Setting elements:
– Heating curve
– Setting knob
Display; one operating line is assigned to each setting
Buttons for selecting and readjusting the values:
Selecting the next operating line below
Selecting the next operating line above
Decreasing the displayed value
Increasing the displayed value
Adopting a setting value:
The setting value is adopted by selecting the next operating line (or: Press Info button or one
of the operating mode buttons)
Entering --.- or --:-- :
Press
or until the required display appears
Block jump function:
To select a single operating line quickly, two button combinations can be used:
Press
and for selecting the next line block above
Press
and for selecting the next line block below