I-T-E Compression Connectors (CCM800, CCN1200)
25
Figure 3
K. Position connector tang on top of the circuit breaker
terminal pad and secure with 3/8-16 X 11/2 in. socket
head cap screw and conical spring washer Conical
spring washer is to be installed with convex side of
washer toward underside of screw head (Figure 4).
Torque screw to 228 in. lb.
NOTE: When using this kit for ampacities less than 1200A or
where only one or two connectors are to be mounted to
the terminal pad, insert spacers provided in kit between
spring washer and compression lug. (Figures 4a, 4b, 4c
and 4d).
Figure 4