I-T-E TELEMAND
®
Electric Motor Operator
45
General
The motor operated mechanism is designed to open, close
and reset a circuit breaker or switch by remote control. The
customer must supply the circuit breaker or switch normally
ON and OFF push buttons, external wiring, a control power
source, and all control logic. Consult the wiring diagram
(Figure 3, page 47) for a typical control connection.
The motor operator is hinged for opening to the left or right
dependent on catalog number designation. The “L” suffix
means the motor operator is hinged to the left. A motor
operator hinged to the right uses no suffix.
NOTE: For automatic reset operation a separate auxiliary
contact must be provided by the customer. See page for
more details.
Operator Selection
AAAA
AAAA
AAAA
AAAA
AAAA
AAA
A
AAA
A
AAA
A
AAAA
A
AAA
A
AAA
A
AAA
AAA
AA
A
AA
A
AA
A
AAAA
A
AAA
A
AAA
A
AAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAAA
AAA
A
AAA
A
AAA
A
Motor
Operator
Frame
For Use With: I-T-E Circuit
Breakers and Switch Types
MOMN6120
MOMN6120L
MOMN6240
MOMN6240L
MD, ND MD6, HMD6 CMD6 SMD6
SHMD6 SCMD6, ND6, HND6,
CND6 SND6, SHND6, SCND6,
MD6-ETI. CMD6-ETI
Installation
A. Turn off and lock out all power supplying circuit breaker
and motor operator before installing or servicing.
B. Attach the circuit breaker to its mounting surface using
the mounting hardware (1) supplied with the motor
operator (Figure 2).
C. Remove the four shield screws (2) and two lug shields (3)
(Figure 1).
D. Cut out the two 0.563 in. x 1.44 in. long knockouts and
replace the shields.
E. Open the motor operator cover and attach the motor
operator to the circuit breaker using the spacers (4) and
screws (5) provided (Figure 2).