7/25 
Building Technologies    CC1N7101en 
HVAC Products    27.11.2008 
Type summary (other types of burner controls on request) 
The type references given below apply to the LME… burner control without plug-in 
base and without flame detector. For ordering information on plug-in bases and other 
accessories, refer to «Ordering». 
 
Flame detector 
Type 
reference 
Main 
voltage 
tw 
approx. 
s 
t1 
min.
s 
TSA
max.
s 
t3n 
approx.
s 
t3 
approx.
s 
t4 
approx.
s 
t10 
min. 
s 
3)
 
t11 
min. 
s 
1)
 
t12 
min. 
s 
1)
 
Repe-
tition 
For 
replacing of 
Burner controls for 1-stage burners (up to 120 kW output) 
LME11.230A2 
AC230V 
2.5 20 3  2  2  ---  5  --- --- 3x 
--- 
Ionization probe 
(ION) 
LME11.330A2 
AC230V 
2.5 30 3  2  2  ---  5  --- --- 3x 
--- 
 
Burner controls for 2-stage burners, without actuator control 
LME21.130A1 
AC 120 V 
2.5 7 3  2  2  8  5 --- --- --- 
LGB21.130A17 
 
LME21.130A2 
AC 230 V 
2.5 7 3  2  2  8  5 --- --- --- 
LGB21.130A27 
LMG21.130B27 
LME21.230A2 
AC 230 V 
2.5 20 3  2  2  8  5  --- --- --- 
LGB21.230A27 
LMG21.230B27 
LME21.330A1 
AC 120 V 
2.5 30 3  2  2  8  5  --- --- --- 
--- 
 
LME21.330A2 
AC 230 V 
2.5 30 3  2  2  8  5  --- --- --- 
LGB21.330A27 
LMG21.330B27 
LME21.350A1 
AC 120 V 
2.5 30 5  4  2  10  5  --- --- --- 
LGB21.350A17 
 
LME21.350A2 
AC 230 V 
2.5 30 5  4  2  10  5  --- --- --- 
LGB21.350A27 
LMG21.350B27 
Ionization probe 
(ION) or flame 
detector 
QRA... 
4) 
with 
AGQ3...A27 
LME21.550A2 
AC 230 V 
2.5 50 5  4  2  10  5  --- --- --- 
LGB21.550A27 
 
 
Burner controls for 2-stage burners, with actuator control 
LME22.131A2 
AC 230 V 
2.5 7 3  2  3  8  3 12 12 --- 
LGB22.130A27 
LMG22.130B27 
LME22.231A2 
AC 230 V 
2.5 20 3  2  3  8  3  12 12 --- 
--- 
 
LME22.232A2 
AC 230 V 
2.5 20 3  2  3  8  3 16.5 16.5 --- 
LGB22.230A27 
LMG22.230B27 
LME22.233A2 
AC 230 V 
2.5 20 3  2  3  8  3  30 30 ---  LMG22.233B27 
LME22.331A1 
AC 120 V 
2.5 30 3  2  3  8  3  12 12 --- 
--- 
 
LME22.331A2 
AC 230 V 
2.5 30 3  2  3  8  3  12 12 --- 
LGB22.330A27 
LMG22.330B27 
Ionization probe 
(ION) or flame 
detector  
QRA... 
4)
 with 
AGQ3...A27 
LME22.333A2 
AC 230 V 
2.5 30 3  2  3  8  3  30 30 --- 
--- 
 
 
Burner controls for 2-stage burners, with actuator control 
LME23.331A2 
AC 230 V 
2.5 30 3  2  3  8  3  12 12 ---  LGB32.330A27 
Blue flame 
detector QRC… 
LME23.351A2 
AC 230 V 
2.5 30 5  4  1  10  3  12 12 --- 
LGB32.350A27
 
 
Legend 
 
tw  Waiting time  1)  Max. running time available for actuator «SA»  
TSA  Safety time    The actuator running time must be shorter 
t1  Prepurge time  2)  t22 + response time of flame relay 
t3  Preignition time  3)  Max. 65 s 
t3n  Postignition time  4)  Only used for AC 230 V 
t4  Interval between ignition «Off» and «BV2»     
t10  Specified time for air pressure signal     
t11  Programmed opening time for actuator «SA»     
t12  Programmed closing time for actuator «SA»     
t22  2nd safety time