8/25 
Building Technologies    CC1N7101en 
HVAC Products    27.11.2008 
Type summary (other types of burner controls on request) [cont´d] 
 
Flame detector 
Type refer-
ence 
Main 
voltage 
tw 
min. 
s 
t1´ 
min.
s 
TSA 
max.
s 
t3n 
approx.
s 
t3 
approx.
s 
t4 
approx.
s 
t22 
approx. 
s 
Repetition  For replacing of 
Burner controls for atmospheric burners 
LME41.051A2 
AC 230 V 
2,5 1  5  4  1  ---  ---  3x  --- 
LME41.052A2 
AC 230 V 
2,5 1  5  4  10  ---  ---  X  --- 
LME41.053A2 
AC 230 V 
2,5 10  5  4  1  ---  ---  X  --- 
LME41.054A2 
AC 230 V 
2,5 1  5  4  1  ---  ---  X  --- 
LME41.071A2 
AC 230 V 
2,5 10  10  9  1  ---  ---  X  --- 
LME41.091A2 
AC 230 V 
2,5 1  10  9  10  ---  ---  X  --- 
Ionization probe (ION) 
or flame detector 
QRA... 
4) 
with 
AGQ3...A27 
LME41.092A2 
AC 230 V 
2,5 1  10  9  1  ---  ---  X  --- 
 
 
       
Burner controls for atmospheric burners 
LME44.056A2 
AC 230 V 
16 9  5  4  2  10  5  ---  LGB41.255A27 
LME44.057A1 
AC 120 V 
16 9  5  4  2  10  8  ---  LGB41.258A17 
Ionization probe (ION) 
or flame detector 
QRA... 
4) 
with 
AGQ3...A27 
LME44.057A2 
AC 230 V 
16 9  5  4  2  10  8  ---  LGB41.258A27 
 
Legend 
 
tw  Waiting time  1)  Max. running time available for actuator «SA»  
TSA  Safety time    The actuator running time must be shorter 
t1´  Purge time  2)  Max. 65 s 
t3  Preignition time  3)  Max. 65 s 
t3n  Postignition time  4)  Only used for AC 230 V 
t4  Interval between ignition «Off» and «BV2»     
t10  Specified time for air pressure signal     
t11  Programmed opening time for actuator «SA»     
t12  Programmed closing time for actuator «SA»     
t22  2nd safety time