9/25 
Building Technologies    CC1N7101en 
HVAC Products    27.11.2008 
Technical data 
Mains voltage  AC 120 V +10% / -15% 
AC 230 V +10% / -15% 
Mains frequency  50...60Hz ±6% 
Power consumption  12VA 
External primary fuse (Si)  Max. 10A (slow) 
Mounting position  Optional 
Input current at terminal 12  Max. 5A 
Weight Approx. 160g 
Safety class 
I 
Degree of protection  IP40 (to be ensured through mounting) 
Perm. cable length terminal 1  Max. 1m at a line capacitance of 100pF/m  
(max. 3m at 15pF/m) 
Perm. cable length from QRA… to 
AGQ3…A27 (lay separate cable) 
Max. 20m at 100pF/m 
Remote reset laid separately  Max. 20m at 100pF/m 
Perm. cable length terminals 8 and 10  Max. 20m at 100pF/m 
Perm. cable lengths other terminals  Max. 3m at 100pF/m 
 
Perm. terminal load  At cosϕ ≥ 0.6  At cosϕ = 1 
- Terminal 3  Max. 2.7A  
(15A for max. 0.5s → only LME2…) 
Max. 3A 
- Terminals 4, 5, 7 and 9 (11) Max. 1.7A  Max. 2A 
- Terminal 10  Max. 1A  Max. 1A 
 
Storage 
DIN EN 60721-3-1 
Climatic conditions  Class 1K3 
Mechanical conditions  Class 1M2 
Temperature range  -20...+60°C 
Humidity <95% r.h. 
Transport 
DIN EN 60 721-3-2 
Climatic conditions  Class 2K2 
Mechanical conditions  Class 2M2 
Temperature range  -20...+60°C 
Humidity <95% r.h. 
Operation 
DIN EN 60 721-3-3 
Climatic conditions  Class 3K3 
Mechanical conditions  Class 3M3 
Temperature range  -20...+60°C 
Humidity <95% r.h. 
 
Condensation, formation of ice and ingress of water are not permitted! 
* The designed lifetime is not the warranty time specified in the Terms of Delivery 
 
General unit data 
Environmental 
conditions