Technical data
Mains voltage AC 120 V +10% / -15%
AC 230 V +10% / -15%
Mains frequency 50...60 Hz ±6%
Power consumption 12 VA
External primary fuse (Si) Max. 10 A (slow)
Mounting position Optional
Input current at terminal 12 Max. 5 A
Weight Approx. 160 g
Safety class
I
Degree of protection IP40 (to be ensured through mounting)
(if RJ11 jack is not covered, only IP10)
Perm. cable length terminal 1 Max. 1 m at a line capacitance of 100 pF/m
(max. 3 m at 15 pF / m)
Perm. cable length from QRA… to
AGQ3…A27 (lay separate cable)
Max. 20 m at 100 pF / m
Remote reset laid separately Max. 20 m at 100 pF / m
Perm. cable length terminals 8 and 10 Max. 20 m at 100 pF / m
(lay separate cable)
Perm. input voltage terminals 6 and 11 AC 120 V +10% / -15%
AC 230 V +10% / -15%
Perm. cable lengths other terminals Max. 3 m at 100 pF / m
Possible input current terminals 6 and 11 0.5 mA
Current rating At cosϕ 0.6 At cosϕ = 1
- Terminal 3 Max. 2.7 A
(15 A for max. 0.5 s only LME2…)
Max. 3 A
- Terminals 4, 5, 7 and 9 Max. 1.7 A Max. 2 A
- Terminal 10 Max. 1 A Max. 1 A
Signal cable
Color white
Unshielded
Conductor 4 x 0.141 mm²
Supplier Reference:
Hütter
http://www.huetter.co.at/telefonkabel.htm
Order number: on request
Location Under the burner hood (extra measures
required for compliance with SKII EN
60730-1)
Storage
DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Transport
DIN EN 60 721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature range -20...+60 °C
Humidity <95% r.h.
Operation
DIN EN 60 721-3-3
Climatic conditions Class 3K3
Mechanical conditions Class 3M3
Temperature range -20...+60 °C
Humidity <95% r.h.
Condensation, formation of ice and ingress of water are not permitted!