08/2005 Overview of Alarms
2-917
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
Reactions: - NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Remedy: • The blocking frequency in drive MD 5514: SPEED_FILTER_1_SUPPR_FREQ
• or in drive MD 5210: OUTPUT_VCTRL_FIL_1_SUP_FREQ
• or in drive MD 5213: OUTPUT_VCTRL_FIL_2_SUP_FREQ
• or in drive MD 5268: FFW_FCTRL_FIL_1_SUP_FREQ
• or in drive MD 5288: OUTPUT_FIL_1_SUP_FREQ must be less than the reciprocal
value of two speed controller cycle times MD 5001: SPEEDCTRL_CYCLE_TIME, i.e. less
than 1 / (2 * MD 5001 * 31.25 microsec).
Program Con-
tinuation:
Clear alarm with the RESET key in all channels. Restart part program.
310758 Axis %1 drive %2 natural frequency > Shannon frequency
Parameters: %1 = NC axis number
%2 = Drive number
Definitions: The natural frequency of a speed setpoint filter is greater than the Shannon sampling fre-
quency from the sampling theorem.
Reactions: - NC not ready.
- The NC switches to follow-up mode.
- Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
- NC Stop on alarm.
- Channel not ready.
Remedy: The natural frequency in Hz of a speed setpoint filter must be less than the reciprocal
value of two speed controller cycles.
Speed filter:
MD 5520 * 0.01 * MD 5514 < 1 / ( 2 * MD 5001 * 31.25 microsec)
• BSP natural frequency drive MD 5520: SPEED_FILTER_1_BS_FREQ
• BSP blocking frequency drive MD 5514: SPEED_FILTER_1_SUPPR_FREQ
• Speed controller cycle drive MD 5001: SPEEDCTRL_CYCLE_TIME
Program Con-
tinuation:
Clear alarm with the RESET key in all channels. Restart part program.
310759 Axis %1 drive %2 bandwidth numerator larger than double blocking frequency
Parameters: %1 = NC axis number
%2 = Drive number
Definitions: The bandwidth numerator of a speed or manipulated variable setpoint filter is greater than
twice the blocking frequency.
This error message is only issued for the general bandstop filter if:
• Speed filter 1:
• MD 5516 > 0.0 or
• MD 5520 <> 100.0

Other manuals for Siemens MCP 398C

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens MCP 398C and is the answer not in the manual?

Siemens MCP 398C Specifications

General IconGeneral
BrandSiemens
ModelMCP 398C
CategoryControl Systems
LanguageEnglish

Related product manuals