08/2005 Overview of Alarms
2-931
© Siemens AG, 2005. All rights reserved
SINUMERIK 840D sl/840D/840Di/810D Diagnostics Guide (DA), 08/2005 Edition
%2 = Size of the area in bytes
Definitions: An incorrect logical base address was specified for a digital or analog input. Either no slot
has been configured for this base address or the requested area extends beyond the end
of the slot.
For length =1 it is a digital output,
For length =2 it is an analog output.
Reactions: - Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Remedy: Enter correct base addresses in the machine data:
• For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
• For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
• NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text
and contact the control system manufacturer.
Program Con-
tinuation:
Switch control OFF - ON.
380072 Profibus DP: output slot for base address %1 (size %2) not allowed
Parameters: %1 = Logical base address of the requested area
%2 = Size of the area in bytes
Definitions: An incorrect logical base address was set for a digital or analog output, the area is resides
in the access range of the PLC (PIQ, base addresses < 256).
For length =1 it is a digital output,
For length =2 it is an analog output.
Reactions: - Channel not ready.
- NC Start disable in this channel.
- Interface signals are set.
- Alarm display.
Remedy: Only use addresses >= 256 for output slots.
Enter correct base addresses in the machine data:
• For length=1: Correct machine data MN_HW_ASSIGN_DIG_FASTOUT.
• For length=2: Correct machine data MN_HW_ASSIGN_ANA_FASTOUT.
• NCK restart
If the error cannot be eliminated by this procedure, please make a note of the error text
and contact the control system manufacturer.
Program Con-
tinuation:
Switch control OFF - ON.
380075 PROFIBUS DP: DP I/O failure bus %2 slave %1
Parameters: %1 = Slave address
%2 = Number of the affected bus
Definitions: Failure of a PROFIBUS slot used by the NCK for digital or analog I/O.
Reactions: - Alarm display.
Remedy: Check that the PROFIBUS slave is operating correctly (all slaves must be included in the
bus, green LED).
Program Con-
tinuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
380500 Profibus-DP: fault on drive %1, code %2, value %3, time %4