PARAMETER LISTING.....................................................
Parameter Function Range Default Unit
*P085 Motor rating plate nominal power 0.12-400.0 kW (hp =
North America)
P086 Motor current limit 0-200 100 %
P087 Motor PTC enable 0-1 0
P088 Automatic calibration 0-1 0
P089 Stator resistance 0.01-199.99 Ω
P091 Serial link slave address 0-30 0
P092 Serial link baud rate 3-7 6
P093 Serial link time-out 0-240 0 sec
P094 Serial link nominal system setpoint 0-150.0 50.00 (60,00 =
North America)
Hz
P095 USS compatibility 0-2 0
P101 Operator for Europe or North America
(goes to either 0 or 1 after first energised)
0-2 2
P111 Inverter power rating 1.1-90.0 kW/hp
P112 Inverter type 1-10
P113 Drive model 0-47
P121 Enable/disable RUN button 0-1 1
P124 Enable/disable \ and ] buttons 0-1 1
P128 Fan switches-off delay time (MMV only) 0-600 120 Sec
P131 Frequency setpoint 0.00-150.0 - Hz
P132 Motor current 0.0-590.0 - A
P133 Motor torque 0-250 - %
P134 DC link voltage 0-1000 - V
P135 Motor speed 0-9999 - RPM
P136 Output voltage 0-1000 - V
P140 Most recent fault code 0-255 -
P141 Most recent fault code - 1 0-255 1
P142 Most recent fault code - 2 0-255 -
P143 Most recent fault code - 3 0-255 -
*P199 Access to Expert mode 0 or 1 0
P201 PID closed loop mode 0-1 0
P202 P gain 0.0-999.9 1.0
P203 I gain 0.00-99.9 0
P204 D gain 0.0-999.9 0
P205 Sample interval (x 25ms) 1-2400 1
P206 Transducer filtering 0-255 0
P207 Integral capture range 0-100 100 %
P208 Transducer type 0-1 0
P210 Transducer reading 0.00-100.00 - %
P211 0% setpoint 0.0-100.00 0.0
P212 100% setpoint 0.0-100.00 100.00
P220 PID frequency cut-off 0-1 0
P321 Minimum analog frequency for analog setpoint 2 0-150.00 0.00 Hz
P322 Maximum analog frequency for analog setpoint 2 0-150.0 50.00 (60,00 =
North America)
Hz
P323 Analog input 2 type 0-2 0
P356 Digital input 6 configuration 0-24 6
P386 Inertia compensation 0.0-20.0 1.0
P720 Direct input/output functions 0-7 0
P721 Analog input 1 voltage 0.0-10.0 - V
P722 Analog output 1 current 0.0-20.0 0.0 mA
P723 State of digital inputs 0-3F -
P724 Relay output control 0-3 0
P725 Analog input 2 voltage 0.0-10.0 - V
P726 Analog output 2 current. Models above 7.5kW only 0.0-20.0 0.0 mA
P910 Local/Remote mode 0-4 0
P922 Software version 0.00-99.99 -
P923 Equipment system number 0-255 0
P930 Most recent fault code 0-255 -
P944 Reset to factory default settings 0-1 0
* Indicates Basic Parameters
Value depends on rating of the invert