Page #6 background imageLoading...
Page #6 background image
NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
6
NXAirS description
6. Module type
NXAirS consists of various module types which can be freely combined according to the requirements.
The following module types are available:
Circuit-breaker module
Disconnecting module
Metering module
Switch-disconnector module
Busbar sectionalizer
6.1 Circuit breaker module
The Circuit-breaker module is the basic module type of NXAirS. The circuit-breaker module panel NXAirS can fulfill
the function of “outgoing feeder” or”distribution”. It can carry or switch on/off all the rated currents and short-circuit
currents specified on the respective rating plates.
Busbar
Breaker module panel SION
Low-voltage plug connector with interlock between SION module and panel
Mechanism box of control cable
Current transformers
Fixed Current transformers
Disconnection truck with lower PT
Make-proof earthing switch
Connection compartment with arresters
Connection compartment with over-voltage protection device
Motor-driven earthing-switch
6.2 Disconnecting module
The disconnecting module panel is an additional module to the basic module. It's used to carry electrical power. It can
not switch on electrical power. The withdrawable part in the disconnecting module NXAirS is therefore protected by a
padlock against arbitrary operation (standard construction).
Busbar
Disconnecting module panel
Low-voltage plug connector with mechanical interlock between module and panel
Mechanism box of control cable
Current transformers
Fixed Current transformers
Make-proof earthing switch
Connection compartment with arrester
Connection compartment with over-voltage protection device
6.3 Switch-disconnector module
The Switch-disconnector module is used to switch on the station transformer, and it is equipped with fuses to protect
the transformers. Degree of continuity: LSC 2A
Busbar
Fixed Switch-disconnector
Low-voltage plug connector with mechanical interlock
Mechanism box of control cable
Current transformers
Make-proof earthing switch
6.4 Metering module
The metering module with PT is used to meter busbar voltage
Busbar
Withdrawable module
Low-voltage plug connector with mechanical interlock
Optionally, can be with 3 PT installed, and can be with fuse installed or not
Basic components
Option
Basic components
Option
Basic components
Option
Basic components

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens NXAirS and is the answer not in the manual?

Siemens NXAirS Specifications

General IconGeneral
BrandSiemens
ModelNXAirS
CategorySwitch
LanguageEnglish

Related product manuals