NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
8
NXAirS description
7.1 High voltage compartment
Contain Circuit Breaker module, switch-disconnector module, disconnection module, or Metering module
Open door from the left
Shutters for covering the contacts automatically when the Circuit--Breaker module, Disconnecting module or Metering
module is taken out from the panel. The shutters can be padlocked separately .The shutter mechanism for the
connection compartment is located on the right inside of the panel. The shutter mechanism for the busbar
compartment is located on the left inside of the panel.
Metallic cable channel is for placing control cable
Pressure release upwards
There is natural Ventilation on the door of high-voltage compartment for the rated current≥2500A panel
Motor-driven cassettee
Heating device
7.2 Circuit Breaker module SION
SION is withdrawable module
Integration construction, with reliable mechanical interlock
Mechanical switch status indicator on the circuit-breaker
Reliable interlock between module and panel
The drive unit of circuit-breaker
Separated contacts
Mechanical interlock
Interface of mechanical operation
Low-voltage plug connector with mechanical interlock
Electric magnet for closing
Mechanical status indicator of spring
Primary working current release or tripping coil
Operation cycle counter
Indicate device of switch status
Electrical tripping prevention
Voltage sensitivity resistance module when the auxiliary voltage>60V
Electromagnetic interlock
The secondary release
Low-voltage release
CT drive release
Circuit breaker
- Circuit breaker can be operated by button or electronic remote controller. The energy for the “open-close-open”
procedure (quick automatical reclose) is stored in the close /opening spring, usually the spring is driven by an electric
machine, which can be replaced by a special tool when the operation voltage is not available. Spring indicator shows
pring status. Switch status indicator shows circuit-breaker status. Counter shows the operation time.
Disconnection function.
- Circuit-breaker can be pulled from the test position to the service position (or in reverse) with a special tool. The test
position or service position of the circuit-breaker can be observed through an inspection window.
The operation mechanism of the feeder earthing switch.
- Insert the operation tool in the operation opening and turn to earth the feeder, switch status indicator shows status
of the earthing switch. To avoid wrong operation, there are mechanical interlocks between the different operation
mechanisms.
The following releases send command code to the Interlock mechanism to control the opening and closing of the circuit-
breaker.
Primary and secondary current release (optional)
Basic features
Option
Module type
Module SION features
Basic features
Option
Module operation