10 / 14
Siemens RDF301. / RDF301.50 / RDF600KN CE1N3171en
Building Technologies Semi flush-mount room thermostats with KNX communications 2012.10-04
Operational data Switching differential, adjustable
Heating mode (P30)
Cooling mode (P31)
2 K (0.5...6K)
1 K (0.5...6K)
Setpoint setting and range
Comfort (P08)
Economy (P11-P12)
Protection (P65-P66)
21°C (5...40 °C)
15°C/30°C (OFF, 5...40 °C)
8°C/OFF (OFF, 5...40 °C)
Multifunctional input X1/X2
Input X1 default value (P38)
Input X2 default value (P40)
Selectable 0...8
3 (Operating mode
switchover)
1 (External temperature
sensor)
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
0…49 °C
< ± 0.5 K
± 3.0 K
Settings and display resolution
Setpoints
Current temperature value displayed
0.5 °C
0.5 °C
Environmental conditions Operation
Climatic conditions
Temperature
Humidity
As per IEC 721-3-3
Class 3K5
0...50 °C
<95 % r.h.
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
As per IEC 721-3-2
Class 2K3
25...60 °C
<95 % r.h.
Class 2M2
Storage
Climatic conditions
Temperature
Humidity
As per IEC 721-3-1
Class 1K3
25...60 °C
<95 % r.h.
Standards and directives
conformity
EMC directive
Low-voltage directive
2004/108/EC
2006/95/EC
C-tick conformity to EMC emission standard
AS/NZS 61000.6.3: 2007
Reduction of hazardous substances 2002/95/EC
Product standards
Automatic electrical controls for household and
similar use
Special requirements for temperature-dependent
controls
Electronic control type
Home and Building Electronic Systems
EN 60730–1
EN 60730–2-9
2.B (micro-disconnection on
operation)
EN 50090-2-2
Electromagnetic compatibility
Emissions (residential)
Immunity (industrial and residential)
IEC/EN 61000-6-3
IEC/EN 61000-6-2
Safety class II as per EN 60730
Pollution class Normal
Degree of protection of housing IP 30 as per EN 60529