Siemens Industry, Inc.
Building Technologies Division
P/N 315-033270-126
*PINS 6 & 7 ON THE PORT 2 CONNECTOR
MUST BE STRAPPED TO ENABLE PORT3.
1
2
3
4
5
9
10
6
7
8
DATA FROM FOREIGN SYSTEM
DATA TO FOREIGN SYSTEM
TO COMMON OF FOREIGN SYSTEM
DO NOT USE
DO NOT USE
DATA FROM FOREIGN SYSTEM
DATA TO FOREIGN SYSTEM
TO COMMON OF FOREIGN SYSTEM
DO NOT USE
DO NOT USE
PORT1
PORT3*
Figure 10
FSI RS-232 Connection
NOTES:
1. 14-18 AWG.
2. 25 feet Max.
3. Power Limited to NFPA 70
per NEC 760.
4. Maximum Voltage 20V peak
to peak.
5. Maximum Current 25mA.
6. Not supervised.
7. Foreign System must be UL
EDP or ETI listed.
8. Only ONE FSI (RS-232 or
RS-485) connection allowed
per RPM.
The PAL-1 requires a standby power source in the event of the loss of primary input
power (AC mains). Refer to Figure 9 for the connection of a UPS to meet this require-
ment.
Figure 9
UPS Wiring Diagram
1
H
2
GND
3
N
4
H
5
N
9
H
10
GND
11
N
6
H
7
GND
8
N
120 VAC
UTILITY
POWER
SOURCE
DO NOT
USE
DO NOT
USE
POWER TO
PRINTER
120 VAC
SEE NOTE 4
AC
INPUT
FAIL
TERMINAL BLOCK
LOCATED ON
UPS SYSTEM
CONTROL BOARD
TO HTRI-S/-D/-R INPUT TERMINALS.
PROGRAM AS NORMALLY CLOSED
TROUBLE CAUSING INPUT IN ZEUS.
REFER TO INSTALLATION
INSTRUCTIONS, P/N 315-033300.
BATTERY
FAIL
1
NO
2
C
3
NC
4
NO
5
C
6
NC
NOTES:
1. All wires 14 AWG min.,
600V insulation.
2. Wiring to the printer must
be 14 AWG min., 600V
insulation in conduit.
3. Use the UPS ICS Lifeline
Model 9300057.
4. Standby Power require-
ments: 120 VAC, 0.6A for 24
hours.