Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity
Levels
IEC 60068-2-30 Humidity (Damp
Heat, Cyclic)
Test Db 95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1 Vibration 2 g @ 10-150 Hz Class 2
Shock 30 g @ 11 ms Class 2IEC 60255-21-2
Bump 10 g @ 16 ms Class 1
Long Life (Random Vibration) IEC 61373
Shock
Category 1 Class B
IEC 60255-21-3 Seismic Method A Level 2
MIL-STD-810G Altitude 12192 m (40000 ft)
@ 40 °C, 90 minutes
RUGGEDCOM RX1501
Installation Manual, 05/2020, C79000-G8976-1054-17
57