Siemens Building Technologies Basic Documentation RVD110, RVD130 CE1P2381E
HVAC Products 1 Summary 27.05.2004
Outside sensor QAC32 (sensing element NTC 575 at 20 °C)
For the room temperature:
Suited are PPS-compatible temperature sensors. The following type is presently
available:
Digital room temperature sensor QAA10
For the d.h.w. temperature and the secondary flow temperature of the heat ex-
changer:
Strap-on temperature sensor QAD22
Immersion temperature sensor QAE22...
1.3.2 Suitable room units
Room unit QAW50
Room unit QAW70
1.3.3 Suitable valve actuators
All Siemens actuators with the following features can be used:
Electric or electrohydraulic actuators with a running time of 10...900 seconds
3-position control
Operating voltage AC 24 V...230 V
1.3.4 Communication
The RVD110 / RVD130 are designed exclusively for standalone operation. There is no
bus connection facility.
1.3.5 Documentation
Type of documentation Classification number
Data Sheet RVD110/RVD130 N2381
Operating Instructions RVD110/RVD130 B2381
Installation Instructions RVD110/RVD130 G2381
Data Sheet QAW50 N1635
Installation Instructions QAW70 G1637
Data Sheet QAW70 N1637
Data Sheet QAA10 N1725