Siemens Building Technologies Basic Documentation RVD110, RVD130 CE1P2381E
HVAC Products 11 Function block Space heating 27.05.2004
2381B03
E
H
T
Vw
T
Rw
/ /
+50 K
-50 K
L
T
Rx
1
/
2
1
s
s
s
T
AM
Generation of setpoint with weather-compensated control with room temperature influence
* Multiplier Operating line 5 = setting of heating curve slope
E Room authority Operating line 69 = setting of heat gains
H Heating curve Operating line 70 = setting of room temperature influence (gain factor)
L Limiter Operating line 71 = parallel displacement of heating curve
S Heating curve slope
T
AM
Composite outside temperature
T
Rw
Room temperature setpoint
T
Rx
Room temperature
T
Vw
Flow temperature setpoint
11.5 Control
11.5.1 Weather-compensated control
Prerequisites for this type of control:
Outside sensor connected
No room unit connected or, if connected, room authority set to 0 (minimum)
The compensating variable for weather-compensated control is the composite outside
temperature. The assignment of the flow temperature setpoint to the compensating
variable is made via the set heating curve. In that case, the room temperature will not
be taken into consideration.
Main application of this type of control are plants or buildings in which
several rooms are occupied at the same time
none of the rooms is suited as a reference room for the room temperature
11.5.2 Room temperature-compensated control
.
Prerequisites for this type of control:
Room unit connected
No outside sensor connected
If no outside sensor is connected, the setting on operating line 70 (room temperature
influence) is inactive.
The compensating variable for room temperature-compensated control is the deviation
of the actual room temperature from the setpoint from which the room authority is gen-
erated. In addition, an assumed outside temperature of 0 °C is used for generating the
setpoint.
When there is no room temperature deviation, the controller maintains the flow tem-
perature setpoint generated by the heating curve slope at an outside temperature of
0 °C