Siemens Building Technologies Basic Documentation RVD110, RVD130 CE1P2381E
HVAC Products 15 Function block Extra legionella functions 27.05.2004
If a maximum d.h.w. charging time has been set, it also acts here. If the legionella set-
point is not reached, the legionella function will be interrupted and resumed on comple-
tion of the maximum charging time.
The legionella setpoint will not be affected by the maximum of the d.h.w. temperature
setpoint.