EasyManua.ls Logo

Siemens S55624-H137 - User Manual

Siemens S55624-H137
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
A6V11521633_en--_b
Smart Infrastructure
2020-11-09
Flush-mounted sensors and room operator units for KNX
PL-Link
QMX3.P35H..., QMX3.P38H...
Communicating sensors, switches and room operator units with KNX PL-Link (for
Desigo™ Room Automation)
Functions (depending on type)
160 x 128 pixel touch screen
Energy efficiency function (“Green Leaf”)
Built-in room temperature sensor
LCD display for room temperature, CO
2,
humidity, PM2.5, operating mode etc.
User interface for lighting, blinds and scene control (QMX3.P38H)
KNX PL-Link (plug & play)
Powered over KNX PL-Link
Sound buzzer
White or black housing
Question and Answer IconNeed help?

Do you have a question about the Siemens S55624-H137 and is the answer not in the manual?

Summary

Communicating Sensors and Room Operator Units

Use and Compatibility

Mechanical Design

Type Summary

Product Documentation

Security

National Safety Regulations

Adherence to national safety regulations for personal injury and property damage prevention.

Engineering

Mounting and Installation

Mounting Guidance

Guidance on wall and flush mounting of devices, recommended height, and placement.

Installation Instructions

Instructions for KNX PL-Link wiring and use of correct cables for the bus.

Operation

Operational Setting

How operation and display depend on the room automation station's control program.

Main Page Display: Lighting, Blinds, and Scenes

Manual Commissioning (KNX PL-Link)

Commissioning Steps

Procedure for commissioning room operator units via the room automation station using specific tools.

Maintenance

Disposal

Warranty

Technical Data

Power Supply Specifications

Details on operating voltage and power consumption for the room automation station.

Operating Data

Information on temperature sensor type, measuring range, and accuracy.

Display Information

Type of display and information content provided by the LCD touch screen.

Ports and Interface

Specifications for the KNX/PL-Link port, baud rate, plug, and cable type.

Ambient Conditions and Protection Classification

Standards, Directives and Approvals

General Product Information

Diagrams

Connection Diagrams

Illustrations showing KNX/PL-Link connections and device wiring.

KNX;PL-Link Plug Details

Details on the KNX PL-Link plug, including wire color coding for positive and negative.

Tool Connection

Instructions for connecting the ABT tool to the room automation station or room unit.

Dimensions

Summary

Communicating Sensors and Room Operator Units

Use and Compatibility

Mechanical Design

Type Summary

Product Documentation

Security

National Safety Regulations

Adherence to national safety regulations for personal injury and property damage prevention.

Engineering

Mounting and Installation

Mounting Guidance

Guidance on wall and flush mounting of devices, recommended height, and placement.

Installation Instructions

Instructions for KNX PL-Link wiring and use of correct cables for the bus.

Operation

Operational Setting

How operation and display depend on the room automation station's control program.

Main Page Display: Lighting, Blinds, and Scenes

Manual Commissioning (KNX PL-Link)

Commissioning Steps

Procedure for commissioning room operator units via the room automation station using specific tools.

Maintenance

Disposal

Warranty

Technical Data

Power Supply Specifications

Details on operating voltage and power consumption for the room automation station.

Operating Data

Information on temperature sensor type, measuring range, and accuracy.

Display Information

Type of display and information content provided by the LCD touch screen.

Ports and Interface

Specifications for the KNX/PL-Link port, baud rate, plug, and cable type.

Ambient Conditions and Protection Classification

Standards, Directives and Approvals

General Product Information

Diagrams

Connection Diagrams

Illustrations showing KNX/PL-Link connections and device wiring.

KNX;PL-Link Plug Details

Details on the KNX PL-Link plug, including wire color coding for positive and negative.

Tool Connection

Instructions for connecting the ABT tool to the room automation station or room unit.

Dimensions

Overview

This document describes the Siemens Flush-mounted sensors and room operator units for KNX PL-Link, specifically models QMX3.P35H... and QMX3.P38H.... These devices are designed for Desigo™ Room Automation and serve as communicating sensors, switches, and room operator units.

Function Description

The room operator units integrate into a KNX PL-Link system, providing comprehensive control and monitoring capabilities for room automation. They function as a central interface for users to interact with various room functions. The core functionality is determined by the room automation station, which dictates the behavior of both the LCD display and the touch screen.

Key functions include:

  • Measurement and Indication: The devices measure and display room temperature, humidity, PM2.5, and CO2 levels. They can also indicate external information such as outdoor temperature and humidity, depending on the application.
  • Operation of Room Functions: Users can operate various room functions directly from the unit. This includes controlling lighting, blinds, and scene settings, particularly with the QMX3.P38H models.
  • Energy Efficiency: An integrated "Green Leaf" function promotes energy efficiency.
  • User Interface: The units feature a 160 x 128 pixel touch screen and an LCD display to show relevant information and provide an intuitive user interface.
  • KNX PL-Link Integration: Designed for KNX PL-Link, these devices offer plug & play functionality, simplifying installation and commissioning. They are powered directly over the KNX PL-Link bus.
  • Sound Buzzer: A sound buzzer provides audible feedback for user interactions or alerts.
  • Housing Options: The units are available in white (RAL9003) or black (Pantone Black C) housing to suit different aesthetic preferences.

Important Technical Specifications

Power Supply:

  • Operating Voltage: KNX / PL-Link DC 21...30 V. The device receives power from the connected room automation station via the KNX/PL-Link interface.
  • Power Consumption (at DC 24 V):
    • QMX3.P35H: Max. 15 mA
    • QMX3.P35H-BSC: Max. 15 mA
    • QMX3.P38H: Max. 15 mA
    • QMX3.P38H-BSC: Max. 15 mA

Operating Data (Temperature Sensor - all types):

  • Measuring Element: NTC resistance sensor
  • Measuring Range: 0...50 °C
  • Measuring Accuracy (5...30 °C): < 0.8 K
  • Measuring Accuracy (25 °C): < 0.5 K

Display:

  • Type: LCD touch screen (160 x 128 pixels)
  • Information Displayed: Room temperature, humidity, CO2, PM2.5, outdoor temperature, outdoor humidity, setpoint adjustment, operating mode, auto or manually selected fan speed, occupancy/vacancy status, and scenes.

Ports/Interface:

  • Type of Port: Between room automation station and operator unit: KNX/PL-Link
  • Baud Rate: 19.2 kbps
  • Standard KNX Plug: Wire diameter 0.8 mm, max. 1.0 mm (solid conductors only)
  • Cable Type: Solid conductors 2-core, twisted pair
  • Single Cable Length (from room automation station to room operator unit): < 1000 m
  • Cables: Must comply with KNX specifications (refer to TRA Install. manual, A6V10361918).

Ambient Conditions and Protection Classification:

  • Protection Standard (EN 60529): IP30
  • Insulation Protection Class: III
  • Climatic Ambient Conditions:
    • Storage (EN 60721-3-1): Class 1K3 (Temperature: -5...45 °C, Humidity: 5...95 % r.h.)
    • Transport (packaged for transport) (EN 60721-3-2): Class 2K3 (Temperature: -25...70 °C, Humidity: 5...95 % r.h.)
    • Operation (EN 60721-3-3): Class 3K5 (Temperature: -5...45 °C, Humidity: 5...95 % r.h.)
  • Mechanical Ambient Conditions:
    • Storage (EN 60721-3-1): Class 1M2
    • Transport (EN 60721-3-2): Class 2M2
    • Operation (EN 60721-3-3): Class 3M2

General:

  • Color Type (front housing): White (RAL9003) or Black (Pantone Black C)
  • Weight with Package: 163 g (for all QMX3.P35H, QMX3.P35H-BSC, QMX3.P38H, QMX3.P38H-BSC models)
  • Dimensions: 88.2 mm (height) x 86.2 mm (width) x 17.2 mm (depth) for the visible part, with a mounting depth of 3.3 mm. The base plate has dimensions of 60 mm x 60 mm for conduit box mounting.

Usage Features

Mechanical Design and Mounting:

  • Mounting: The devices are designed for wall and flush mounting with a common square conduit box (not included, must be ordered separately).
  • Base Plate: The base plate has screw holes compatible with common conduit boxes. Screw head height must not exceed 3 mm.
  • Integrated Components: The device incorporates a KNX PL-Link plug, a tool plug, sensor element, and an LCD touch panel. The cable can be hidden within the conduit box. A KNX plug is enclosed with the devices.
  • Recommended Height: 1.50 m above the floor.
  • Placement Restrictions: Do not mount devices in recesses, shelves, behind curtains or doors, or above/near heat sources. Avoid direct solar radiation and drafts.
  • Sealing: Seal the conduit box or installation tube to prevent air currents from affecting sensor readings.
  • Installation: Only electrical installers should install the base plate and the KNX PL-Link plug. Refer to the Desigo TRA installation guide (A6V10361918) for KNX PL-Link wiring, allowed cables, and cable length. Use correct cables for the KNX PL-Link bus.
  • Wiring: Do not interchange the wires of the KNX PL-Link cable (red terminal for +, gray terminal for -). The devices are protected against faulty wiring, but communications will not work if wires are interchanged. Do not connect the KNX / KNX PL-Link bus to the tool plug; only the tool should be connected there.

Operational Setting:

  • Dependence on Control Program: Operation and display of the room operator unit depend on the control program of the room automation station.
  • Main Page Display: The main page displays HVAC functions for all types, showing current temperature, setpoint, operating mode (AUTO), and fan speed. For QMX3.P38H models, the main page also displays lighting, blinds, and scene controls.
  • Icons: Various icons are used to indicate inside/outside temperature, temperature/humidity/CO2/PM2.5 display, operating mode (Comfort, Pre-comfort, Economy, Protection), heating/cooling status, green leaf for energy efficiency, operational elements, relative/absolute setpoint, locked status, fan speed (AUTO, OFF, 1, 2, 3), navigation, occupancy state, programming mode, connection test, and reset to factory settings.
  • Lighting, Blinds, and Scenes (QMX3.P38H, QMX3.P38H-BSC): Dedicated icons allow control of individual lights (Light A, B, C, D), blinds (Blind 1, 2, 3, 4), and scene settings such as Meeting, Presentation, Break, Occupied/Unoccupied, Cleaning, Do not disturb, and Amusement.

Manual Commissioning (KNX PL-Link):

  • Process: All commissioning is done via the room automation station using SSA-DNT or ABT. ABT is not connected directly to the room operator unit.
  • Steps:
    1. Connect SSA-DNT or ABT to the room automation station and activate the online commissioning function.
    2. Load the web page "KNX PL-Link identification" and activate the identification function. The room automation station will wait for a signal.
    3. On the room operator unit, enter Engineering mode by pressing a specific area (blank space on bottom right for unconfigured units, or the dedicated icon for QMX3.P35H/QMX3.P38H) for at least 5 seconds.
    4. The "Engineering" page will display.
    5. Press "Program." The display changes from "Off" to "On." The tool identifies the unit and assigns an address.
    6. After commissioning, the display automatically changes to "Off."

Connecting the Tool:

  • The ABT can be connected directly to the room automation station or to the room unit using a tool cable and the OCI702 service interface (refer to data sheet A6V10438951) to load applications or for service purposes.
  • The tool plug is a 2.5 mm jack. The RJ45 plug of the tool cable has specific pin assignments for CE+, KNX, CE-, KNX, Voltage 16 V, ID pin, and GND.

Maintenance Features

Cleaning:

  • Cleaning Agents: The device can be cleaned with off-the-shelf, solvent-free cleaning agents.
  • Cleaning Tools: Use only a soft, damp cloth. Do not use mechanical aids such as rough sponges or similar materials.

Disposal:

  • Electronic Device: The device is considered an electronic device and must be disposed of in accordance with European Guidelines. It should not be disposed of as domestic garbage.
  • Disposal Channels: Dispose of the device through designated channels and comply with all local and currently applicable laws and regulations.

Security:

  • National Safety Regulations: Failure to comply with national safety regulations may result in personal injury and property damage. Always observe national provisions and comply with appropriate safety regulations.
  • Electrical Safety: The devices are not protected against accidental connection to AC 230 V. Only electrical installers should handle installation.

Siemens S55624-H137 Specifications

General IconGeneral
BrandSiemens
ModelS55624-H137
CategoryAccessories
LanguageEnglish