SIPART
Electropneumatic positioners
SIPART PS2 with and without HART
Edition 10/2013
SIPART PS2 with and without HART
Operating Instructions 10/2013
A5E00074631-11
4 019169 188074
A5E00074631-11
Operating Instructions
Get more information
www.siemens.de/processautomation
www.siemens.de/sipartps2
Answers for industry.

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers

  • N
    Nicholas WilliamsAug 17, 2025
    What causes maximum angle span exceeded error in Siemens Valve Positioners?
    • N
      natalieperezAug 17, 2025
      If the maximum angle span is exceeded on your Siemens Valve Positioner, it could be because the effective lever arm isn't adjusted to the actuator travel or the mounting kit isn't correctly installed. Try positioning the carrier pin at a larger stroke value and check the mounting kit. Alternatively, consider using the Siemens SIPART PS2 electropneumatic positioner with a swivel area of 185° (special version).
  • M
    Morgan BestAug 20, 2025
    How to switch Siemens Valve Positioners from manual to auto mode?
    • E
      Ethan CrawfordAug 20, 2025
      If your Siemens Valve Positioner is in manual mode, switch to "AUTO" mode.
  • C
    Christopher JacobsonAug 22, 2025
    What to do if there is a control deviation in Siemens Valve Positioners?
    • R
      rachel31Aug 22, 2025
      If your Siemens Valve Positioner shows a control deviation, it could be due to several reasons. First, check if there's sufficient compressed air supply. Also, ensure the mounting kit is correctly installed. Lastly, a blocked valve could also be the cause. Eliminate any of these potential causes to resolve the deviation.
  • S
    Susan SchultzAug 25, 2025
    How to fix initialization errors in Siemens Valve Positioners?
    • S
      Sara GrahamAug 26, 2025
      If your Siemens Valve Positioner displays initialization errors, the issue might stem from insufficient compressed air, incorrect mounting of the kit, or a blocked valve. To resolve this, identify and eliminate the cause, then restart the initialization process.
  • C
    Caleb PageAug 28, 2025
    What to do if measuring range of position detection exceeded in Siemens Valve Positioners?
    • C
      Caitlin BryanAug 28, 2025
      If the measuring range of position detection is exceeded on your Siemens Valve Positioner, it could be due to the swivel area of the valve being larger than 110°, installing the positioner on a different actuator without re-initialization, or worn end positions of the valve. Check the mounting kit for proper installation and inspect for any wear. Then, start the initialization process.
  • L
    Lawrence AcevedoAug 30, 2025
    Why is value below minimum angle span displayed on Siemens Valve Positioners?
    • K
      Kara MeyerAug 30, 2025
      If your Siemens Valve Positioner shows a value below the minimum angle span, it might be because the effective lever arm isn't adjusted to the actuator travel, or the mounting kit isn't correctly installed. Try positioning the carrier pin at a smaller stroke value and check the mounting kit.
  • R
    Reginald WheelerSep 2, 2025
    What to do if a pneumatic leakage is present in Siemens Valve Positioners?
    • C
      Charlene HunterSep 2, 2025
      If a pneumatic leakage is present in your Siemens Valve Positioner, you should remedy the pneumatic leak of the actuator and the piping.
  • C
    Chad DavisSep 5, 2025
    How to deactivate button lock on Siemens Valve Positioners?
    • T
      Tanya HobbsSep 5, 2025
      If the button lock is activated on your Siemens Valve Positioner, switch the digital input (DI).
  • F
    fwagnerSep 7, 2025
    What does 'Approach valve position activated through digital input' mean on Siemens Valve Positioners?
    • J
      jamesflemingSep 8, 2025
      If the 'Approach valve position' is activated through digital input (DI) on your Siemens Valve Positioner, this is a configured response. Change the parameters until the message no longer appears.
  • C
    Christina CastroSep 12, 2025
    How to disable write protection with user PIN on Siemens Valve Positioners?
    • D
      Darlene TorresSep 12, 2025
      To disable write protection on your Siemens Valve Positioner, use the user PIN LOCK 2457.

Summary

Safety information

Requirements for safe use

Emphasizes observing instructions and specifications for safe device operation and maintaining integrity.

Improper device modifications

Warns against unauthorized modifications, detailing risks to personnel, system, environment, and warranty.

Use in hazardous areas

Specifies qualifications for personnel and safety precautions for operating the device in hazardous environments.

Installing;mounting

Mounting the linear actuator

Provides detailed requirements and procedures for mounting the positioner on linear actuators.

Mounting the part-turn actuator

Details the requirements and step-by-step procedure for mounting the positioner on part-turn actuators.

Connection

Electric

Covers basic electrical safety, cable gland torque, and wiring diagrams for various device versions.

Operating

Commissioning

Sequence of automatic initialization

Details the phases and structured charts for automatic initialization of linear and part-turn actuators.

Commissioning linear actuators

Covers preparation, setting the transmission ratio, connecting the positioner, and initialization procedures.

Commissioning part-turn actuators

Explains preparation, setting adjustment angle, and automatic/manual initialization for part-turn actuators.

Functional safety

Range of applications for functional safety

Specifies suitability for SIL 2 requirements and single-acting actuators with spring return.

Safety function

Details the depressurization safety function and triggers for 2-wire and 3/4-wire connections.

Safety Integrity Level (SIL)

Explains SIL levels based on PFDAVG and achievable SIL for Type A devices based on SFF and HFT.

Settings

States that no special parameter settings are required for the safety function itself.

Safety characteristics

Lists conditions for system use, including low demand rate, blocked operation, and single-acting actuator return.

Parameterizing;addressing

Description of parameters

Details specific parameters, including actuator type, angle of rotation, stroke, initialization, and various monitoring functions.

Alarm, error, and system messages

Fault correction

Provides a diagnostics guide for fault identification and detailed remedial measures tables.

Service and maintenance

Basic safety instructions

Outlines essential safety precautions for repair, maintenance, and handling of the device.

Technical data