Alarm, error, and system messages 
  10.4 Fault correction 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
227 
 
Remedial measures table 2 
 
•  "CPU testt" blinks on the display 
approximately every 2 seconds. 
•  Piezo valve does not activate. 
•  Water in the pneumatic block (due 
to wet compressed air) 
•  At an early stage, this fault can be 
rectified with a subsequent 
operating using dry air, if required, 
in a temperature cabinet at 50 to 
70°C. 
•  Otherwise: Repair 
•  In the manual and automatic 
modes, the actuator cannot be 
moved or can be moved only in one 
direction. 
•  Moisture in the pneumatic block 
•  Piezo valve does not activate (a 
gentle click sound is not audible 
when the "+" or "-" buttons are 
pressed in the manual mode.) 
•  The screw between the shrouding 
cover and the pneumatic block has 
not been tightened firmly or the 
cover got stuck. 
•  Tighten the screw firmly; if required, 
rectify the deadlock. 
•  Dirt (swarf, particles) in the 
pneumatic block 
•  Repair or a new device; clean 
and/or replace the built-in fine 
screens. 
•  Deposits on the contacts between 
the electronic printed circuit board 
and the pneumatic block may 
develop due to abrasion owing to 
continuous loads resulting from 
strong vibrations. 
•  Clean all contact surfaces with 
spirit; if required, bend the 
pneumatic block contact springs. 
Repair/Upgrading (Page 233)