Alarm, error, and system messages 
  10.4 Fault correction 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
229 
 
Remedial measures table 4 
 
•  In stationary automatic mode 
(constant setpoint) and in manual 
mode, both piezo valves continually 
switch alternately, and the actuator 
oscillates around a mean value. 
•  Sticking friction of the packing gland 
from the control valve or actuator 
too large 
•  Reduce friction or increase dead 
zone of positioner (parameter 
"dEbA") until the oscillation stops. 
•  Looseness (play) in the 
positioner/actuator/control valve 
system 
•  Part-turn actuator: Check for firm 
seating of set screw on coupling 
wheel. 
•  Linear actuator: Check for firm 
seating of lever on positioner shaft. 
•  Correct any other play between the 
actuator and the control valve. 
•  Actuator too fast  •  Increase actuating times using 
throttle screws. 
•  If a quick actuating time is needed, 
increase the dead zone (parameter 
"dEbA") until the oscillation stops. 
•  Positioner doesn't move control 
valve to the stop (at 20 mA). 
•  Supply pressure too low. Load on 
the feeding controller or system 
output is too low. 
•  Increase supply pressure, insert 
ballast converter 
•  Select 3/4-wire mode 
Cleaning of the screens (Page 232)