Parameterizing/addressing   
9.4 Description of parameters 
  SIPART PS2 with and without HART 
176  Operating Instructions, 10/2013, A5E00074631-11 
 
Description of parameters A through P 
9.4.3.1
 
Description of parameter A 
A. PST - partial stroke test  
Use this parameter to activate the partial stroke test for cyclic or manual testing of 
open/closed and control valves. Set the "On" parameter value to activate the test. Sub-
parameters are displayed. If the sub-parameters are set to the desired parameter values, 
initiate the partial stroke test using: 
●  Buttons on the device 
●  A binary input 
●  Communication 
●  A cyclic test interval 
Sub-parameters are described below. 
The factory setting is "OFF". 
A1.STPOS - starting position  
Use this sub-parameter to define the starting position of the partial stroke test in percent. To 
this end, set the starting position within a range from "0.0" to "100.0". 
The factory setting is "100.0". 
A2.STTOL - starting tolerance  
Use this sub-parameter to define the starting tolerance of the partial stroke test in percent. 
Set the starting tolerance relative to the starting position in a range from "0.1" to "10.0".  
Example: You have set 50% as a starting position and 2% as a starting tolerance. In this 
case, a partial stroke test is initiated during operation only between a current position of 48 
and 52%. 
The factory setting is "2.0". 
A3.STEP - stroke magnitude  
Use this sub-parameter to define the stroke magnitude of the partial stroke test in percent. 
To this end, set the stroke magnitude within a range from "0.1" to "100.0". 
The factory setting is "10.0".