Parameterizing/addressing   
9.4 Description of parameters 
  SIPART PS2 with and without HART 
170  Operating Instructions, 10/2013, A5E00074631-11 
 
Description of parameters 44 
44.AFCT - Alarm function 
This parameter can be used to determine the value at which going above or below a given 
offset or angle will result in a message. The triggering of alarms (limits) is relative to the 
MPOS scale. Alarms are signaled through the alarm module. In addition, alarms can also be 
read out over the HART communicator (optional). 
The direction of action of the binary outputs can be adjusted from "High active" to "Low 
active" for the next system. 
 
Direction of action and hysteresis 
 
 
AFCT = MIN / MAX 
 
AFCT = -MIN / -MAX 
 
AFCT = MIN / MAX 
Way =45 
   
 
AFCT = -MIN / -MAX 
 
 
Note 
If the extended diagnostic is activated using parameter "51.XDIAG" with setting "On2" or 
"On3", then the alarms will no
t be output through the alarm module. Notification through 
HART communication is possible at any time, however.