EasyManuals Logo

Siemens SIPART Series User Manual

Siemens SIPART Series
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #172 background imageLoading...
Page #172 background image
Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
170 Operating Instructions, 10/2013, A5E00074631-11
9.4.2.14
Description of parameters 44
44.AFCT - Alarm function
This parameter can be used to determine the value at which going above or below a given
offset or angle will result in a message. The triggering of alarms (limits) is relative to the
MPOS scale. Alarms are signaled through the alarm module. In addition, alarms can also be
read out over the HART communicator (optional).
The direction of action of the binary outputs can be adjusted from "High active" to "Low
active" for the next system.
Direction of action and hysteresis
Alarm module
Examples
A1
A2
A1 = 48
AFCT = MIN / MAX
A2 = 52
Way =45
Active
Way =50
Way =55
Active
A1 = 48
AFCT = -MIN / -MAX
A2 = 52
Way =45
Active
Way =50
Active
Active
Way =55
Active
A1 = 52
AFCT = MIN / MAX
A2 = 48
Way =45
Active
Way =50
Active
Active
Way =55
Active
A1 = 52
AFCT = -MIN / -MAX
A2 = 48
Way =45
Active
Way =50
Way =55
Active
Note
If the extended diagnostic is activated using parameter "51.XDIAG" with setting "On2" or
"On3", then the alarms will no
t be output through the alarm module. Notification through
HART communication is possible at any time, however.

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART Series and is the answer not in the manual?

Siemens SIPART Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART Series
CategoryAccessories
LanguageEnglish

Related product manuals