Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
161
9.4.2
Description of parameters 6 through 51
9.4.2.1
Description of parameters 6
6.SCUR - Current range of setpoint
This parameter is used to set the current range of the setpoint. The selection of the current
range depends on the type of connection. Parameter value "0 MA" (0 to 20 mA) is only
possible for three-wire and four-wire connections.
The factory setting is "4 MA".
See also
Basic device without Ex protection / in flameproof enclosure "Ex d" (Page 72)
Description of parameters 8 and 9 (Page 162)
9.4.2.2
Description of parameters 7
7.SDIR - Setpoint direction
This parameter is used to set the setpoint direction. The setpoint direction is used to reverse
the direction of action of the setpoint. The setpoint direction is primarily used for single-acting
actuators with the safety setting "up".
The factory setting is "riSE".
See also
Description of parameters 8 and 9 (Page 162)