Parameterizing/addressing 
  9.4 Description of parameters 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
163 
 
Description of parameters 10 and 11 
10.TSUP - Setpoint ramp OPEN 
and 
11.TSDO - Setpoint ramp CLOSED 
The setpoint ramp is effective in automatic mode and limits the speed of change of the 
effective setpoint. When switching from manual to automatic mode, the setpoint ramp is 
used to adjust the effective setpoint to the setpoint occupied by the positioner. 
This smooth switching from manual to automatic mode prevents pressure excess in long 
pipelines. 
The parameter value "TSUP = Auto" means the slower of the two actuating times determined 
during initialization is used for the setpoint ramp. Parameter value "TSDO" then has no 
effect. 
The factory setting is "0". 
 
Description of parameters 12 
12.SFCT - Setpoint function 
This parameter is used to linearize nonlinear valve characteristics. For linear valve 
characteristics, arbitrary flow characteristics are formed. 
See figure in Description of parameters 13 through 33 (Page 164). 
Seven valve characteristics are stored in the positioner and are selected using the "SFCT" 
parameter: 
 
The factory setting is "Lin".