Alarm, error, and system messages   
10.4 Fault correction 
  SIPART PS2 with and without HART 
230  Operating Instructions, 10/2013, A5E00074631-11 
 
Remedial measures table 5 
 
•  Zero point displaces sporadically 
(> 3%). 
•  Impact or shock loads result in 
accelerations so high that the 
friction clutch moves, e.g. due to 
"vapor shocks" in vapor lines. 
•  Rectify the causes for shock loads. 
•  Re-initialize the position controller. 
•  The device function has completely 
failed: No representation on the 
display either. 
•  Electrical auxiliary power supply is 
not adequate. 
•  Check the electrical auxiliary power 
supply. 
•  In case of very high continuous 
loads due to vibrations 
(oscillations): 
•  Screws of the electrical connecting 
terminals may be loosened. 
•  Electrical connecting terminals 
and/or electronic components may 
be knocked out. 
•  Tighten the screws firmly and 
secure using sealing wax. 
•  Repair 
•  For prevention: Install the positioner 
on the damping pads. 
Repair/Upgrading (Page 233)