Connection 
  5.3 Restrictors 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
99 
 
●  Reduce the air output to achieve actuating times of T > 1.5 s for small actuators. Use 
restrictors Y1 
① and Y2 ② for this purpose. 
●  When turned clockwise, they reduce the air output and finally shut it off. 
●  In order to set the restrictors, we recommend closing them and then opening slowly. 
●  In case of double-acting valves, ensure that both restrictors have approximately the same 
setting. 
 
Restrictor Y2, only in the version for double-acting actuators 
Hexagon socket-head screw 2.5 mm 
Figure 5-27  Restrictors 
Pneumatic connection in the flameproof enclosure (Page 95) 
Sequence of automatic initialization (Page 117)