Connection
5.3 Restrictors
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
99
5.3
Restrictors
Reduce the air output to achieve actuating times of T > 1.5 s for small actuators. Use
restrictors Y1
and Y2 for this purpose.
When turned clockwise, they reduce the air output and finally shut it off.
In order to set the restrictors, we recommend closing them and then opening slowly.
In case of double-acting valves, ensure that both restrictors have approximately the same
setting.
Restrictor Y1
Restrictor Y2, only in the version for double-acting actuators
Hexagon socket-head screw 2.5 mm
Figure 5-27 Restrictors
See also
Pneumatic connection in the flameproof enclosure (Page 95)
Sequence of automatic initialization (Page 117)