Alarm, error, and system messages 
  10.4 Fault correction 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
225 
 
 
Fault identification 
Diagnostics guide 
 
Remedial measures, see 
table 
In which mode does a fault occur? 
•  Initialization 
1       
•  Manual and automatic modes 
2  3  4  5 
In which environment and under which boundary conditions does a fault occur? 
•  Wet environment (e.g. strong rain or constant condensation) 
2       
•  Vibrating (oscillating) control valves 
2  5     
•  Impact or shock loads (e.g. vapor shocks or breakaway valves) 
5       
•  Moist (wet) compressed air 
2       
•  Dirty (contaminated with solid particles) compressed air 
2  3     
•  Regularly (reproducible) 
1  2  3  4 
•  Sporadically (not reproducible) 
5       
•  Mostly after a specific operation time 
2  3  5   
Remedial measures table 1 (Page 226) 
Remedial measures table 2 (Page 227) 
Remedial measures table 3 (Page 228) 
Remedial measures table 4 (Page 229) 
Remedial measures table 5 (Page 230)