Technical data
12.4 Controller
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
239
12.4
Controller
Controller
Control unit
• Five-point controller
Adaptive
• Dead zone
dEbA = auto
Adaptive or can be preset
dEbA = 0.1 ... 10 %
Adaptive or can be preset
Analog-to-digital converter
• Scanning time
10 ms
• Resolution
≤ 0.05 %
• Transmission error
≤ 0.2 %
• Temperature influence
≤ 0.1 %/10 K (≤ 0.1 %/18 °F)
Cycle time
• 20 mA/HART device
20 ms
• PA device
60 ms
• FF device
60 ms (min. loop time)
12.5
Certificates, approvals, explosion protection for all device versions
Certificates and approvals
Classification according to pressure
equipment directive (PED 97/23/EC)
For fluid group 1 gases; fulfills requirements in article 3, paragraph 3 (good
engineering practice SEP)
CE conformity The applicable directives and standards applied with their revision levels can
be found in the EC declaration of conformity on the Internet.

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART Series and is the answer not in the manual?

Siemens SIPART Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART Series
CategoryAccessories
LanguageEnglish

Related product manuals