SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
269 
 
Operation with boosters 
Introduction 
In order to shorten the actuating times, it is possible to use a booster between the positioner 
and actuator. The booster increases the air performance. 
With single-acting positioners you require a booster which must be connected to the air 
output Y1. With double-acting positioners you require two boosters which must be connected 
to the air output Y1 and to Y2.  
 
Avoid pressure variations 
Make sure that the booster does not result in pressure variations in the supply air P
z
 on the 
positioner. 
 
Note when selecting the boosters: 
•  Only boosters may be used which do not have a continuous air consumption in the 
setpoint input. 
•  The boosters must not have a follow-up time. 
A stable operating state will not be reached if these two points are not observed. All 
process components involved are subject to faster wear. 
1.  Reduce the air performance. To do this, use the restrictors on the positioner. 
2.  Set the deadband "DEBA" to the largest value permissible for your process. 
3.  Start the initialization process. 
4.  If necessary, adjust the actuating times during the initialization process. 
If the process value on the display does not remain stable or if a constant manipulated 
variable cannot be achieved for a constant setpoint, further optimization of the controller data 
is necessary. This is described in section Optimizing the controller data (Page 110). 
Sequence of automatic initialization (Page 117)