Functional safety
8.6 Maintenance/check
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
145
The average temperature viewed over a long period is 40 °C.
Fault rates are calculated on the basis of a mean time to repair (MTTR) of 8 hours.
In case of a fault, the pneumatic outlet of the positioner is depressurized. A spring in the
pneumatic actuator must move the valve to the pre-defined, safe end position.
A dangerous failure of the positioner is a failure whereby the pressure outlet is not
depressurized or the safety position is not reached when the signal source is 0 mA or the
power supply source is 0 V.
See also
Settings (Page 144)
8.6
Maintenance/check
Interval
We recommend that the functioning of the positioner is checked at regular intervals of one
year.
Checking the safety function
Check the safety function as detailed in chapter "Settings (Page 144)"
Checking safety
Verify the safety function of the entire safety circuit on a regular basis in accordance with
IEC 61508/61511. The test intervals are determined in the course of calculations for each
safety circuit of a system (PFD
AVG
).

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART Series and is the answer not in the manual?

Siemens SIPART Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART Series
CategoryAccessories
LanguageEnglish

Related product manuals