Parameterizing/addressing   
9.4 Description of parameters 
  SIPART PS2 with and without HART 
174  Operating Instructions, 10/2013, A5E00074631-11 
 
Description of parameters 51 
51.XDIAG - Activation of extended diagnostics 
This parameter is used to activate extended diagnostics. At the factory, extended diagnostics 
are deactivated. Parameter "51.XDIAG" is set to "OFF". To activate extended diagnostics, 
there are three modes available: 
●  On1: Extended diagnostics are activated. Threshold 3 error messages will be output over 
the fault message output. 
●  On2: Extended diagnostics are activated. Threshold 2 error messages will be activated 
using alarm output 2. Threshold 3 error messages will also be output over the fault 
message output. 
●  On3: Extended diagnostics are activated. Threshold 1 error messages will be activated 
using alarm output 1. Threshold 2 error messages will be activated using alarm output 2. 
Threshold 3 error messages will also be output over the fault message output. 
 
Note 
Activation of extended diagnostics 
Please note that the parameters of extended diagnostics will only be shown in the 
display, from "A.
PST" to "P. PAVG", following selection of one of the modes "On1" to 
 
In the factory settings, parameters "A.
PST" to "P. PST" are deactivated by default. 
Parameter "51.XDIAG" is set to "OFF
". The corresponding parameters are only displayed 
after you activate the appropriate menu item with "On".
 
With extended diagnostics, the threshold of the error message is displayed using columns in 
addition to the error code. These columns are shown on the display as follows:  
 
Figure 9-6  Display of a threshold 1 error message 
 
Figure 9-7  Display of a threshold 2 error message