Technical data 
  12.8 Option modules 
SIPART PS2 with and without HART 
Operating Instructions, 10/2013, A5E00074631-11 
253 
 
Certificates, approvals, explosion protection for all device versions 
 
For connecting to circuits with the 
following peak values 
U
i
 = 5 V  
I
i
 = 100 mA  
P
i
 = 160 mW  
C
i
 = negligibly small  
i
 
 
Certificates and approvals 
CE conformity  The applicable directives and standards applied with their revision levels can 
be found in the EC declaration of conformity on the Internet. 
 
 
Explosion protection in accordance with 
Intrinsic safety "ia" 
Zone 1:  
 II 2 G  Ex ia IIC T6/T4 Gb 
Zone 21:  
 II 2 D  Ex ia IIIC 110°C Db 
Intrinsic safety "ic" 
Zone 2:  
 II 3 G  Ex ic IIC T6/T4 Gc 
Non-sparking "nA" 
Zone 2:  
 II 3 G  Ex nA IIC T6/T4 Gc 
Permissible ambient temperature 
  T4: -40 ... +90 °C (-40 ... +194 °F)  
T6: -40 ... +60 °C (-40 ... +140 °F)