EasyManuals Logo

Siemens SIPART Series User Manual

Siemens SIPART Series
292 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #255 background imageLoading...
Page #255 background image
Technical data
12.8 Option modules
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
253
12.8.7.3
Certificates, approvals, explosion protection for all device versions
Electrical data
For connecting to circuits with the
following peak values
U
i
= 5 V
I
i
= 100 mA
P
i
= 160 mW
C
i
= negligibly small
L
i
= negligibly small
Certificates and approvals
CE conformity The applicable directives and standards applied with their revision levels can
be found in the EC declaration of conformity on the Internet.
Explosion protection
Ex markings
Explosion protection in accordance with
ATEX
Intrinsic safety "ia"
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 21:
II 2 D Ex ia IIIC 110°C Db
Intrinsic safety "ic"
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
Non-sparking "nA"
Zone 2:
II 3 G Ex nA IIC T6/T4 Gc
Permissible ambient temperature
T4: -40 ... +90 °C (-40 ... +194 °F)
T6: -40 ... +60 °C (-40 ... +140 °F)

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART Series and is the answer not in the manual?

Siemens SIPART Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART Series
CategoryAccessories
LanguageEnglish

Related product manuals