1.YFCT - actuator type  
You can use this parameter to adjust the positioner as per the respective actuator and, if 
required, as per the position sensor used. The following parameter values are available: 
●  YFCT = turn 
Use this parameter value for a part-turn actuator. 
The subsequent parameter "2.YAGL" is automatically set to 90° and cannot be changed. 
●  YFCT = WAY (factory setting) 
Use this parameter value for a linear actuator. The positioner compensates the non-
linearity caused due to the transformation of the linear movement of the linear actuator 
into the rotary movement of the positioner shaft. For this purpose, the positioner is set in 
the factory such that it displays values between "P49.0" and "P51.0" when the lever on 
the positioner shaft is perpendicular to the linear actuator spindle. 
●  YFCT = LWAY 
Use this parameter value for: 
–  An external linear potentiometer on a linear actuator. 
–  An external linear potentiometer on a part-turn actuator with a reverse direction of 
action. 
●  YFCT = ncSt 
Use this parameter value when you use a non contacting sensor on a part-turn actuator. 
●  YFCT = -ncSt 
Use this parameter value when you use a non contacting sensor on a part-turn actuator 
with a reverse direction of action. 
●  YFCT = ncSL 
Use this parameter value when you use a non contacting sensor on a linear actuator. 
●  YFCT = ncSLL 
Use this parameter value when you use a non contacting sensor on a linear actuator for 
which the position is transformed by a lever into a rotary movement. 
 
Note 
The "3.YWAY" parameter is displayed only for "WAY" and "ncSLL".
 
The factory setting is "WAY".