Parameterizing/addressing
9.4 Description of parameters
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
169
BIN1 or BIN2 Contact closes = StoP or -StoP Contact opens.
If the binary input is activated in automatic mode, the piezo valves are blocked. The
actuator remains at the last position. Leakage measurements can be performed in this
way without using the initialization function.
BIN1 or BIN2 = PSt or -PSt
Using binary inputs 1 or 2, a partial-stroke test can be triggered by actuation of your
choice of a normally closed or normally open switch.
BIN1 or BIN2 = OFF (factory setting)
No function
Special function of binary input 1: If binary input 1 is activated in "P-manual mode" by
means of a jumper between terminals 9 and 10, then when the mode button is pushed
the firmware version will be displayed.
If one of the above functions is activated with the "BIN1" and "BIN2" parameters
simultaneously, then: "Blocking" has priority over "uP" and "uP" has priority over "down".

Table of Contents

Other manuals for Siemens SIPART Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART Series and is the answer not in the manual?

Siemens SIPART Series Specifications

General IconGeneral
BrandSiemens
ModelSIPART Series
CategoryAccessories
LanguageEnglish

Related product manuals