Commissioning   
7.5 Commissioning part-turn actuators 
  SIPART PS2 with and without HART 
136  Operating Instructions, 10/2013, A5E00074631-11 
4.  Call the "INITM" parameter. To do this, press the   button twice. The display shows the 
following: 
 
5.  Start the initialization process. Press the 
 button for at least 5 seconds until the display 
shows the following: 
 
6.  The current potentiometer position is output on the display after 5 seconds: 
 
7.  Determine the end position 1 of the actuator. 
8.  Move the actuator to the desired position using the 
 or   button. 
9.  Press the 
 button. The current position of the actuator is applied. The display shows the 
following: 
 
 
 
Note 
Fault message "RANGE" 
The selected end position is beyond t
he permissible measuring range if the "RANGE" 
message is output on the display. 
Correct the settings as follows:  
  Move the friction clutch until the display shows "OK". 
  Press the   button. 
  Move the actuator to another position using the   or   button. 
  Abort the manual initialization process by pressing the   button. 
  Then return to "P manual mode" mode. 
  Correct the actuator travel and the position detection. 
10.Determine the end position 2 of the actuator. Move the actuator to the desired position 
using the 
 or  button.