Commissioning
7.5 Commissioning part-turn actuators
SIPART PS2 with and without HART
Operating Instructions, 10/2013, A5E00074631-11
137
11.Press the button. The current position of the actuator is applied.
12.The initialization process is automatically resumed. Initialization steps "RUN1" to "RUN5"
are output in the bottom line of the display. The following display indicates that the
initialization has been completed successfully:
Aborting the manual initialization process
1. Press the button. The display shows the "INITM" parameter. The positioner is in the
"Configuration" mode.
2. Exit the "Configuration" mode. To do this, press the
button for at least 5 seconds.
3. The software status is displayed.
4. After releasing the
button, the positioner is in "P manual mode". "P manual mode"
means that the positioner has not been initialized.
Overview of device components (Page 23)