48
Internal Accessories
For preliminary installation procedures review procedures
outlined on pages 36 and 37.
1.) Remove the rubber band from the solenoid plunger.
Slide the remote close lever on the closing D-shaft but
do not tighten the set screw at this time (Figure 1 )
2.) Place the return spring over the solenoid plunger and
slide the solenoid over the solenoid plunger (Figure 1).
Remote Close Assembly
3.) Attach the remote close assembly to the mechanism
plate using the (2) # 10 screws provided. The assembly
is aligned by a set-out in the mechanism plate that fits in
a hole in the remote close bracket. Note: Torque screws
to 24-32 in. Ibs.
4.) Align remote close link with solenoid and tighten set
screw (see TOP VIEW Detail in Figure 1). Note: Torque
set screw to 6-8 in. lbs.
Figure 1. Remote Close Accessory and Bracket Mounting
Courtesy of NationalSwitchgear.com