Connection
6.1 Safety when connecting up
SCALANCE W774-1 / W734-1
48 Operating Instructions, 03/2022, C79000-G8976-C325-15
WARNING
Lack of equipotential bonding
If there is no equipotential bonding in hazardous areas, there is a risk of explosion due
to equalizing current or ignition sparks.
Ensure that equipotential bonding is available for the device.
WARNING
Unprotected cable ends
There is a risk of explosion due to unprotected cable ends in hazardous areas.
Protect unused cable ends according to IEC/EN 60079-14.
WARNING
Improper installation of shielded cables
There is a risk of explosion due to equalizing currents between the hazardous area and
the non-hazardous area.
Ground shielded cables that cross hazardous areas at one end only.
Lay a potential equalization conductor when grounding at both ends.
WARNING
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Risk of explosion in hazardous areas
When connecting intrinsically safe and non-intrinsically safe circuits, ensure that the
galvanic isolation is performed properly in compliance with local regulations (e.g. IEC
60079-14).
Observe the device approvals applicable for your country.

Other manuals for Siemens SCALANCE W734-1 RJ-45

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE W734-1 RJ-45 and is the answer not in the manual?

Siemens SCALANCE W734-1 RJ-45 Specifications

General IconGeneral
BrandSiemens
ModelSCALANCE W734-1 RJ-45
CategoryWireless Access Point
LanguageEnglish

Related product manuals