Document No. 129-371
Installation Instructions
April 20, 2007
Page 6 of 8
http://www.sbt.siemens.com/hvp/drives Siemens Building Technologies, Inc.
IP54/NEMA Type 12 SED2s
Table 4. IP54/NEMA Type 12 SED2 Overall Dimensions in Inches (Millimeters).
Frame Size
Overall Dimensions
Height × Width ×
Depth
Mounting
Clearance
Top × Bottom ×
Sides
Mounting
Specification
Tightening
Torque
lb-in (Nm)
Weight
lb (kg)
B
15.2 × 10.6 × 10.6
(385 × 270 × 270)
22
(10)
C
23.9 × 13.8 × 11.2
(606 × 350 × 284)
5.9 × 5.9 × 3.9
(150 × 150 × 100)
4 × M6 Bolts, nuts,
washers
44
(5)
42
(19)
D
27.0 × 142 × 13.9
(685 × 360 × 200)
77
(35)
E
34.8 × 14.2 × 17.8
(885 × 360 × 453)
7.9 × 7.9 × 5.9
(200 × 200 × 150)
115
(13)
105
(48)
F
45.3 × 17.7 × 18.6
(1150 × 450 × 473)
11.8 × 9.8 × 5.9
(300 × 250 × 150)
4× M8 Bolts, nuts,
washers
177
(20)
178
(81)
Frame Size
Vmin Clearance in
Inches (Millimeters)
A, B, C
4
(100)
D, E
11-3/4
(300)
F
13-3/4
(350)
NOTE: In all cases, Smin Clearance is
5-7/8 inches (150 millimeters).
Frame Size B
Frame Size C
0.19
(4.8)
9.1
(230)
13.5
(343)
0.22
(5.5)
12.3
(313)
22.2
(564)
Frame Size D
Frame Size E
Frame Size F
0.59
(15)
43.8
(1112)
15.7
(400)
0.68
(17.5)
25.5
(647)
12.2
(310)
0.68
(17.5)
33.5
(847)
12.2
(310)
VFD0013R1
Figure 7. IP54/NEMA Type 12 SED2 Mounting Dimensions in
Inches (Millimeters).
VFD0144R1
S
min.
SED2
SIEMENS
SED2
SIEMENS
V
min.
S
min.
S
min.
V
min.
Wiring
Tightening Torque for Connection
Terminals
Frame Size A B C D E F
Tightening
Torque
lb-in (Nm)
9.7
(1.1)
13.3
(1.5)
19.9
(2.25)
88.5
(10)
max.
88.5
(10)
max.
442
(50)
Cable Cross-Sections for Power and
Motor Cables
Tables 5 through 7 provide cable cross-sections for
input power cables and for motor cables.