Setting English Deutsch
P0311
0 – 40000
1/min
Rated Motor Speed
Nominal motor speed (rpm) from
rating plate
Motornenndrehzahl
Motornenndrehzahl (1/min)
aus dem Typenschild
P0700[2]
Index 0: Auto
Index I : Hand
Selection of Command Source (on /
off )
1 = BOP
2 = Terminal / Digital Inputs (default)
Wahl von Befehlsquellen
(EIN / AUS)
1 = BOP
2 = Klemmen
(Werkseinstellung)
P1000[2]
Index 0: Auto
Index I : Hand
Selection of Frequency Setpoint
1 = BOP Basis Operation Pannel
2 = Analog Setpoint (default)
Wahl des
Frequenzsollwerts
1 = BOP Basis Operation
Pannel
2 = Analogsollwert
(Werkseinstellung)
P1080 Min. Motor Frequency
Sets minimum motor frequency
(0-650Hz) at which the motor will run
irrespective of the frequency setpoint.
The value set here is valid for both
clockwise and counter clockwise
rotation.
Min. Motorfrequenz
Stellt die minimale
Motorfrequenz
(0-650Hz) ein, mit der der
Motor unabhängig vom
Frequenzsollwert läuft. Der
hier eingestellte Wert gilt für
beide Drehrichtungen
P1082 Max. Motor Frequency
Sets maximum motor frequency (0-
650Hz) at which the motor will run at
irrespective of the frequency setpoint.
The value set here is valid for both
clockwise and counter clockwise
rotation.
Max. Motorfrequenz
Stellt die höchste
Motorfrequenz (0-650Hz)
ein, mit der der Motor
unabhängig vom
Frequenzsollwert läuft. Der
hier eingestellte Wert gilt für
beide Drehrichtungen

Other manuals for Siemens SED2