3VL IEC molded case circuit breakers 
System Manual, 11/2013, 110 0110 - 02 DS 03 
119 
  Parameter assignment / addressing 
 
Setting the parameters 
Settings on the ETU 
 
Note 
Adjusting settings 
The overcurrent release is preset with the maximum settings for the overload release and 
the short
-circuit release. You must adjust these settings to the requirements of the system 
when installing the molded case circuit breakers.
 
Changing the setting values for the overload and short
-circuit releases during operation to a 
value below the present operat
ing value causes instantaneous tripping. 
The protection parameters to be set on the electronic trip unit of the molded case circuit 
breaker depend on the technical environment (switchgear, cables), the network 
configuration, and the type of equipment to be protected. There are no fixed protection 
settings. The protection parameters can be determined by the relevant electrical planning 
engineer.  
The Siemens software tool SIMARIS Design offers a simple, quick and safe solution for 
dimensioning switching and protective devices. 
Internet link to SIMARIS (www.siemens.com/simaris
)  
Tripping characteristic curve and settings parameters 
The time/current characteristic of a trip unit offers the best method for calculating the tripping 
characteristics of a trip unit. The tripping characteristic reflects the response of the circuit 
breaker in the event of a fault, e.g. overload or short-circuit. The time required to trip is 
defined at a specific current. The tripping characteristic is split into different sections. Each 
section reflects the tripping response of the circuit breaker at a specific current level 
Depending on the type of tripping, the trip units can be supplied with or without the S, N, or G 
functions (L, S, I, N, G designations in accordance with IEC 60947-2, Annex K).  
●  L long time delay = overload protection with current-dependent long time delay and 
current-dependent tripping curve (I
2
t = constant) 
●  S short time delay (short-circuit protection with short-time delay) = short-circuit protection 
with current-dependent or current-independent short time delay and current-dependent 
tripping curve (I
2
t
sd
 = constant) 
●  I Instantaneous = short-circuit protection with instantaneous adjustable tripping. 
●  N Neutral protection = protection of the neutral conductor with adjustable, current-
dependent tripping curve. 
●  G Ground fault = ground-fault protection with current-independent short-time delay