Methods of implementing selectivity using circuit breakers
3.5 Zone selective interlocking
Selectivity for 3VA molded case circuit breakers
Configuration Manual, 08/2016, A5E03603181010-01
35
Fault scenario F1
A fault occurs within the protection zone of circuit breaker Q11.
If the short-circuit current is high enough, it is detected by the trip unit of circuit
breaker Q11.
Since Q11 does not receive a "block" signal from Q22, the original delay time
t
sd
= 300 ms is replaced by the shortened delay time t
ZSI
= 50 ms.
Q11 trips after t
ZSI
= 50 ms.
Fault scenario F2
A fault occurs within the protection zone of circuit breaker Q22.
If the short-circuit current is high enough, it is detected by the trip units of circuit breakers
Q11 and Q22.
The zone selective interlocking system causes Q22 to temporarily block Q11.
Q11 retains the original delay time t
sd
= 300 ms.
Since Q22 does not receive a "block" signal, its original delay time t
sd
= 200 ms is
replaced by the shortened delay time t
ZSI
= 50 ms.
Q22 trips after t
ZSI
= 50 ms.
Fault scenario F3
A fault occurs within the protection zone of circuit breaker Q32.
If the short-circuit current is high enough, it is detected by the trip units of circuit
breakers Q11, Q22 and Q32
As a result of the zone selective interlocking system, Q32 temporarily blocks Q22 which
in turn temporarily blocks Q11.
Q11 retains the original delay time t
sd
= 300 ms.
Q22 retains the original delay time t
sd
= 200 ms.
Q32 trips after t
i
= 10 ms if the short-circuit is within the range of the instantaneous short-
circuit protection (I).
Q32 trips after t
ZSI
= 50 ms if the short-circuit is within the range of the short-time delay
short-circuit protection (S).
Fault scenario F4
A fault occurs within the protection zone of circuit breaker Q41.
If the short-circuit current is high enough, it is detected by the trip units of circuit
breakers Q11, Q22, Q33 and Q41.
Since Q41 already trips after t
i
= 10 ms, however, none of the other circuit breakers trip.
The zone selective interlocking and time selectivity systems have no influence on circuit
breaker operation.