EasyManua.ls Logo

Siemens SENTRON - Setting of Circuit Breakers

Siemens SENTRON
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Methods of implementing selectivity using circuit breakers
3.5 Zone selective interlocking
Selectivity for 3VA molded case circuit breakers
36 Configuration Manual, 08/2016, A5E03603181010-01
3.5.2 Setting of circuit breakers
Simaris design, a software program published by SIEMENS, is recommended as a tool for
setting circuit breakers. One of the capabilities of this program is to calculate network short-
circuit values.
Two values – "I
kmax
" and "I
kmin
" – are required to select and set a circuit breaker at the
installation point.
I
kmax
is the maximum potential short-circuit at the point of installation of a circuit breaker;
it is determined on the basis of the 3-pole, 2-pole and 1-pole short-circuit calculations.
I
kmin
is the smallest possible short-circuit in the part of the network to be protected; it is
determined on the basis of the 3-pole, 2-pole and 1-pole short-circuit calculations.
This can refer, for example, to the zone to be protected extending from the circuit breaker
up to the end of the cable/busbar at the load, or up to the next protective device (circuit
breaker or fuse).
The following conditions apply to the selection and setting of circuit breakers:
1. A circuit breaker is selected in terms of its rated ultimate short-circuit breaking capacity
I
cu
according to the value of the highest potentially occurring short-circuit:
I
cu
is equal to or greater than I
kmax
.
2. The short-circuit release is set according to the minimum potentially occurring short-circuit
I
kmin
in the relevant network, whereby the tolerances of releases must be taken into
account. According to IEC 60947-2, 8.3.3.1.2, the maximum permissible tolerance of the
short-circuit release is ±20 %.
3. DIN VDE 0100, Part 410 and IEC 60364-4-41 differentiate between break-times
depending on whether the circuit is a distribution circuit or a final circuit.
In distribution circuits (from the main distribution board to the subdistribution board, for
example), a break-time of 5 s applies in TN systems.
In final circuits (from the distribution board to loads/socket outlets), the break-time is
as follows at a rated AC voltage U
o
= 230 V AC phase conductor to ground:
0.4 s at a rated current 32 A in a TN system
and
5 s at a rated current > 32 A in a TN system.

Table of Contents

Other manuals for Siemens SENTRON

Related product manuals