EasyManua.ls Logo

Siemens SENTRON - Page 37

Siemens SENTRON
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Methods of implementing selectivity using circuit breakers
3.5 Zone selective interlocking
Selectivity for 3VA molded case circuit breakers
Configuration Manual, 08/2016, A5E03603181010-01
37
It is clear from this diagram that selective tripping behavior cannot be implemented using the
highest possible setting of the instantaneous short-circuit release (I) of the upstream
3VA2 630A molded case circuit breaker. While the tripping characteristics in the short-circuit
zone of the two circuit breakers only touch with short-circuits of 5 kA or higher so that partial
selectivity up to 5 kA is afforded, the required protective functions are not provided.
Setting the 3VA2 630A molded case circuit breaker:
The value of I
kmaxA
has been calculated as 20.1 kA at the installation point A.
The 3VA24 molded case circuit breaker for a rated operational current I
rated
= 630 A has a
rated ultimate short-circuit breaking capacity I
cu
= 55 kA at 380 - 415 V AC, which means
that this selection is correct.
The value of I
kmaxB
has been calculated as 7.0 kA and the value of I
kminB
as 2.3 kA at the
installation point B.
However, the setting of the instantaneous short-circuit release of the 3VA2 630 A molded
case circuit breaker is higher than the value of I
kminB
(due to the partial selectivity up to
5 kA), and it is not possible to interrupt this I
kminB
value of 2.3 kA within 5 s.

Table of Contents

Other manuals for Siemens SENTRON

Related product manuals