Selectivity with parallel incoming feeders
5.2 Selectivity with three identical incoming feeders
Selectivity for 3VA molded case circuit breakers
60 Configuration Manual, 08/2016, A5E03603181010-01
5.2 Selectivity with three identical incoming feeders
5.2.1 Fault within the protection zone of the downstream protective device
With three parallel-connected transformers, effective current selectivity can be achieved
because the characteristic displacement factor for the incoming feeder circuit breakers Q1,
Q2 and Q3 is within the range 2 < K
t-I
≤ 3.
Characteristic displacement factor
Total short-circuit current