Certification
6.2EMC and Environmental Type Tests
Test Description Test Levels Severity
Levels
IEC
61000-4-3
Radiated RFI Enclosure
Ports
10 V/m 3
Signal Ports ± 4 kV 4
DC Power
Ports
± 4 kV 4
AC Power
Ports
± 4 kV 4
IEC
61000-4-4
Burst (Fast Transient)
Earth
Ground Ports
± 4 kV 4
Signal Ports ± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
DC Power
Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
IEC
61000-4-5
Surge
AC Power
Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
4
Signal Ports 10 V 3
DC Power
Ports
10 V 3
AC Power
Ports
10 V 3
IEC
61000-4-6
Induced (Conducted) RFI
Earth
Ground Ports
10 V 3
IEC
61000-4-8
Magnetic Field Enclosure
Ports
40 A/m Continuous
1000 A/m for 1 s
DC Power
Ports
30% for 0.1 s
100% for 0.02 s
100% for 0.05 s
IEC
61000-4-29
Voltage Dips and Interrupts
AC Power
Ports
30% for 1 Period
60% for 50 Periods
IEC
61000-4-11
Voltage Dips and Interrupts AC Power
Ports
100% for 5 Periods
100% for 50 Periods
Signal Ports 2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
DC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC
61000-4-12
Damped Oscillatory
AC Power
Ports
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
3
IEC 60255-5 Dielectric Strength Signal Ports 0.5 kV (Fail-Safe
Relay output)
RUGGEDCOM RS900G
Installation Manual, 01/2021, C79000-G8976-1025-08
33