Technical specifications
CPU 1513R-1 PN (6ES7513-1RL00-0AB0)
Equipment Manual, 05/2021, A5E42009333-AC
39
Article number
6ES7513-1RL00-0AB0
Diagnostic buffer
present
Yes
Number of entries, max.
1 000
of which powerfail-proof
500
Traces
Number of configurable Traces
4
Memory size per trace, max.
512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
RUN/STOP LED
Yes
ERROR LED
Yes
MAINT LED
Yes
Connection display LINK TX/RX
Yes
Supported technology objects
Motion Control
No
Controller
PID_Compact
Yes; Universal PID controller with integrated op-
timization
PID_3Step
Yes; PID controller with integrated optimization
for valves
PID-Temp
Yes; PID controller with integrated optimization
for temperature
Counting and measuring
Yes
High-speed counter
No
Standards, approvals, certificates
Suitable for safety functions
No
Ambient conditions
Ambient temperature during operation
horizontal installation, min.
0 °C
horizontal installation, max.
60 °C; Display: 50 °C, at an operating temperature
of typically 50 °C, the display is switched off
vertical installation, min.
0 °C
vertical installation, max.
40 °C; Display: 40 °C, at an operating temperature
of typically 40 °C, the display is switched off
Ambient temperature during stor-
age/transportation
min.
-40 °C
max.
70 °C
Altitude during operation relating to sea level
Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2
000 m, see manual