Technical specifications
CPU 1515R-2 PN (6ES7515-2RM00-0AB0)
Equipment Manual, 11/2019, A5E42009914-AB
41
• Number of configurable Traces
4
• Memory size per trace, max.
512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
• RUN/STOP LED
Yes
• ERROR LED
Yes
• MAINT LED
Yes
• Connection display LINK TX/RX
Yes
Supported technology objects
• PID_Compact
Yes; Universal PID controller with integrated
• PID_3Step
Yes; PID controller with integrated optimization
• PID-Temp
Yes; PID controller with integrated optimization
• High-speed counter
No
Standards, approvals, certificates
Suitable for safety functions
Ambient temperature during operation
• horizontal installation, min.
0 °C
• horizontal installation, max.
60 °C; Display: 50 °C, at an operating tempera-
ture of typically 50 °C, the display is switched off
• vertical installation, min.
0 °C
• vertical installation, max.
40 °C; Display: 40 °C, at an operating tempera-
ture of typically 40 °C, the display is switched off
Ambient temperature during stor-
age/transportation
• min.
-40 °C
• max.
70 °C
Altitude during operation relating to sea level
• Installation altitude above sea level, max.
5 000 m; Restrictions for installation altitudes > 2